Fire Investigation Kit
Fire Investigation Kit
The ION Science Fire Investigation Kit with Tiger or Tiger LT photoionisation detector (PID) has been specifically designed to provide you with all the tools for a convenient, easy-to-use solution for the detection of volatile organic compounds (VOCs) within Fire and Arson Investigation applications.
In suspected arson cases, it is part of the fire investigation to prove that there is no other cause of the fire. The Fire Investigation Kit can be used to detect hydrocarbon compounds such as those found in petrol, alkanes, and cycloalkanes. Fire investigators including the police, consultants and private fire investigators acting on behalf of insurance companies, will search for every type of fire accelerant such as grill lighters, lighter fuel, liquid glue and cleaning agents.
Features
Ultimate Performance
- Detects VOCs from 0 up to 20,000 ppm
- Minimum sensitivity 0.001 ppm (1 ppb)
- Detects over 480 VOCs and toxic compounds
- Fast 2-second response time and quick clear down
Ultimate Safety
- Includes an AA TIGER battery pack for emergency power source during long arson and fire investigations
- Integrated flashlight for dark or dimly lit areas
- Flexi-probe for versatile, practical detection of VOCs in hard-to-reach places
Specification
Minimum Resolution*: | 1 ppb or 0.001 mg/m3 |
Maximum reading**: | 20,000 ppm or 20,000 mg/m3 |
Response time: | T90 < 2 seconds |
Accuracy***: | ± 5 % display reading ± one digit |
Lamps: | 10.6 eV Krypton PID lamp (standard.) 10.0 eV and 11.7 eV lamps available |
Intrinsically safe approvals | - II1GExiaIICT4Ga - Tamb = – 15 °C ≤Ta ≤ +45 °C (with lithium ion battery pack) - Tamb = – 15 °C ≤Ta ≤ +45 °C (with alkaline battery pack) - ITS09ATEX26890X IECEx ITS 10.0036X - 3193491 conforms to UL Std. 913, 61010-1 & Certified to CAN/CSA Std. C22.2 No. 61010-1 - Class 1 Division 1. Approval for Groups A, B, C & D, T4 |
Protection | - Designed to IP65 (heavy rain) - EMC tested to EN61326- 1:2006, EN50270:2006 & CFR 47:2008 Class |